Skip to content

Y403-11-L LoRa Automatic Relay Wireless Interlocking Controller Datasheet

Y403-11-L
Y403-11-L product image

Contents

  1. Overview
  2. Ordering Information
  3. Key Features
  4. Technical Specifications
  5. Interfaces and Indicators
  6. Mechanical and Environmental
  7. Installation and Wiring
  8. Important Notes

1. Overview

The Y403-11-L is a LoRa-based automatic relay wireless interlocking controller. Each node automatically selects the best communication path and forwards switching signals to other nodes, extending overall communication distance. It is well suited for coordinated control scenarios such as emergency stop systems and tunnel lighting.

Y403-11-L operation diagram

Operating Logic

  • When the DI on any node is closed, the DO on all nodes, including the local node, energizes
  • The outputs on all nodes reset only after the DI on every node returns to open
  • Nodes automatically relay signals and select the best route to extend communication distance

Typical Applications

Emergency stop systems, tunnel lighting control, underground facility monitoring, and coordinated safety systems


2. Ordering Information

Model Naming

text
Y403-11-L
  |   |  `-- L: LoRa wireless communication
  |   `----- 11: 1DI/1DO configuration
  `--------- Y403: automatic relay interlocking controller series

Package Contents

Qty.Item
1Y403-11-L module
1470 MHz magnetic-mount antenna
1DIN rail clip
1Quick reference guide
1Warranty card

3. Key Features

  1. Automatic relay forwarding - Nodes automatically select the best communication path and forward signals
  2. Interlocking control - A trigger from any node drives all linked nodes, including the local node
  3. OR logic output - All outputs reset only when every node input returns to open
  4. Long-range communication - Up to 5000 m in open area, with relay-based range extension
  5. Scalable expansion - Supports large-scale node expansion through automatic relaying
  6. Wide supply range - 9 to 36V DC with reverse-polarity protection
  7. Relay output - 1 x SPDT relay, rated at AC 277V 5A / DC 28V 5A
  8. Universal DI - Supports dry contact and NPN inputs
  9. Status indication - LEDs for power, relay link, input, and output status
  10. Industrial design - Hardware watchdog and 35 mm DIN rail mounting

4. Technical Specifications

Wireless

ParameterSpecification
Frequency band398 to 525 MHz
Communication range5000 m (open area)
Relay extensionExtended through node-to-node relaying
Antenna connectorSMA
Standard antenna470 MHz magnetic-mount antenna

Electrical

ParameterSpecification
Supply voltage9 to 36V DC
Max. power consumption1W
Input typeNPN signal / dry contact
Output typeSPDT relay
Output ratingAC 277V 5A / DC 28V 5A
Operating temperature-20 to +85 degC
Operating humidity10% to 90% RH, non-condensing

5. Interfaces and Indicators

Interface Summary

InterfaceDescription
AntennaSMA connector for LoRa antenna
PowerDC 9 to 36V input with reverse-polarity protection
InputPassive switch input (DI + COM)
OutputRelay output (NO + COM + NC)

LED Indicators

LEDFunctionStatus
PowerSystem statusOn after power-up
NetworkRelay link statusOn when the relay communication link is established
InputInput statusOn when DI is closed
OutputOutput statusOn when the relay is energized

6. Mechanical and Environmental

Mechanical Specifications

ParameterSpecification
Dimensions88 x 37 x 59 mm
WeightApprox. 50 g
Mounting35 mm DIN rail
Protection ratingIP20
Housing materialFlame-retardant plastic

7. Installation and Wiring

Input Wiring

Mechanical switches (maintained switch, float switch, relay contact):

  • Connect directly between DI and COM
  • No external power supply is required

NPN signal:

  • Emitter -> COM
  • Collector -> DI
  • Do not connect an external voltage source to the input terminal

Output Wiring

Direct load (<= 1 kW resistive load):

  • Wire the load in series with the relay output

High-power load (> 1 kW):

  • Use an AC contactor or external power relay

Installation Notes

  1. Install the antenna vertically in an open area, about 2 m above ground.
  2. Keep the unit away from large metal structures.
  3. Tighten the antenna connector securely.
  4. Mount the unit inside the control cabinet on a 35 mm DIN rail.
  5. Position nodes strategically to achieve the best automatic relay coverage.
  6. Leave enough space for ventilation.

Relay Expansion

  • Nodes automatically select the best communication path and can relay traffic for other nodes.
  • New nodes can join the existing automatic relay system without complex manual setup.
  • Direct node-to-node range is up to 5000 m in open area, with longer reach available through relay paths.

8. Important Notes

  1. Communication mode - Half-duplex communication, not intended for hard real-time control.
  2. Frequency range - Recommended operating range is 398 to 525 MHz. Performance may degrade outside this range.
  3. Antenna placement - Install the antenna vertically in an open area and keep it away from metal obstructions.
  4. Relay latency - Multi-hop relay paths may introduce additional delay. Confirm timing requirements before deployment.
  5. Interlocking logic - All node outputs reset only after every node input returns to open.

  • Manufacturer: Hunan YenGear Tech Co., Ltd.
  • Address: Room 21014, Building 1, Fudi Xingguang Tiandi, Yingxin Road, Yuhua District, Changsha, Hunan, China
  • Email: hi@yengear.com