Skip to content

Y301-880 I/O Module Specification

Y301-880 Product Image

Contents

  1. Overview
  2. Ordering Information
  3. Key Features
  4. Technical Specifications
  5. Interfaces and Pinout
  6. Mechanical and Environmental
  7. Automation Rules

1. Overview

The Y301-880 is the flagship model in the Y301 family. It combines eight opto-isolated digital inputs and eight high-power relay outputs in a 145 x 90 x 40 mm enclosure, delivering the highest Modbus RTU I/O density in the series for PLC expansion, building automation, and large-scale telemetry systems.

ModelDIDOAITypical Role
Y301-88088 (SPDT)-Multi-zone digital automation

Product Highlights

  • Highest I/O density in the Y301 series for digital-only control
  • Independent indicators for all 16 channels plus system status
  • Robust automation firmware with up to 16 local rules and output retention

2. Ordering Information

2.1 Model Naming

Y301-XYZ

  • XYZ: function combination (880 = 8DI + 8DO + 0AI)

2.2 Interface Options

All models are available with the following serial interfaces:

InterfaceDescription
RS485Standard version for Modbus RTU multi-drop networks
RS232Optional version for point-to-point communication
TTLOptional on selected models for direct MCU integration

2.3 SKU Matrix

SKUDescription
Y301-8808 DI + 8 DO, high-density digital I/O module

2.4 Package Contents

Module, digital quick reference guide, and warranty card. Optional accessories include a DIN clip, USB-to-RS485 converter, 24 VDC power supply, and shielded RS485 wiring kit.


3. Key Features

  1. 16-point digital I/O - Eight dry/wet contact DI channels plus eight SPDT relay outputs
  2. High-power relays - Each channel is rated for 277 VAC / 10 A or 28 VDC / 10 A with independent COM/NO/NC terminals
  3. Automation engine - Up to 16 local rules covering follow, pulse, timer, logic, and schedule modes
  4. Scalable addressing - Software Modbus address 1-255 plus a 5-bit DIP offset for panel deployments
  5. Industrial-grade build - 5-36 VDC input, -40 to +85 C, hardware watchdog, Reload button, and surge-protected communication

4. Technical Specifications

4.1 Electrical and Environmental

ParameterSpecification
Supply voltage5-36 VDC
Typical current260 mA @ 12 V
Maximum current350 mA @ 12 V (all relays energized)
Operating temperature-40 to +85 C
Humidity5-95% RH, non-condensing

4.2 Digital Input

ItemSpecification
Channel count8
TypeDry/wet contact, opto-isolated
Voltage range5-36 V (wet contact mode)
Input current<5 mA per channel
Sampling rate100 Hz
Pulse counter32-bit per channel
Debounce5-255 ms (default 50 ms)

4.3 Digital Output

ItemSpecification
Channel count8 x SPDT relays
Contact rating277 VAC 10 A / 28 VDC 10 A
Minimum load10 VAC 10 mA
Switching time<10 ms operate / <5 ms release
Electrical life100k cycles at rated load
Output retentionNone / soft reboot / full retention

4.4 Communication

ItemSpecification
InterfaceRS485 (2-wire), optional RS232 or TTL
ProtocolModbus RTU slave
Baud rate600-230400 bps (default 9600)
Slave address1-255 (software) + DIP offset 0-31

5. Interfaces and Pinout

5.1 Terminal Overview

GroupDescription
PowerV+, V- screw terminals + DC 5.5 x 2.1 mm jack
DIP switchSW1-SW5 (binary address offset)
ReloadHold 3-15 s to restore factory defaults
DICOM+, COM-, DI1-DI8
DONCn / COMn / NOn for channels 1-8
CommunicationA/B/GND (RS485) or TX/RX/GND (RS232/TTL)

5.2 Wiring Guidelines

  • Use 20-16 AWG power wiring with a 2 A upstream fuse.
  • For dry-contact DI, bridge COM+ to the target DI through the external contact.
  • For wet-contact DI, connect the external 5-36 V reference to COM-.
  • For relay outputs driving inductive loads, add an RC snubber for AC loads or a flyback diode for DC loads.
  • For RS485, use shielded twisted pair, terminate both ends with 120 ohm resistors, and keep a common reference ground.

6. Mechanical and Environmental

Y301-880 dimensions

ItemValue
Dimensions145 x 90 x 40 mm
Mounting35 mm DIN clip or screw slots
ProtectionIP20
HousingUL94 V-0 flame-retardant plastic

Keep at least 20 mm clearance above and below, 10 mm on each side, and 60 mm in front for wiring and airflow.


7. Automation Rules

ModeDescription
DI followDO mirrors one or more DI states
Pulse outputConfigurable ON/OFF pulse width
Delay controlProgrammable ON/OFF delay
Cyclic togglePeriodic ON/OFF cycling
Timer/scheduleCalendar-based activation window
Button modeMomentary push-button behavior
Logic modeAND/OR/XOR logic combination
Watchdog modeAutomatically resets the DO when the timeout condition occurs
  • Up to 16 rules total, with up to 2 rules per DO channel
  • Rules run locally without host polling
  • When enabled, output retention stores the last automation state

  • Manufacturer: Hunan YenGear Tech Co., Ltd.
  • Address: Room 21014, Building 1, Fudi Xingguang Tiandi, Yingxin Road, Yuhua District, Changsha, Hunan, China
  • Email: hi@yengear.com
  • Website: www.yengear.com