Skip to content

Y301-880 I/O Module Specification

Y301-880 Product Image

Unified Modbus & Automation Reference: Y301 Series Modbus Technical Manual

Document Control

ItemDetail
VersionV1.0.0
Release DateNovember 2025
Product CategorySerial I/O Module

Table of Contents

  1. Overview
  2. Ordering Information
  3. Key Features
  4. Technical Specifications
  5. Interface & Pin Description
  6. Mechanical & Environmental
  7. Automation & Linkage Rules

1. Overview

Y301-880 is the flagship of the Y301 family, combining eight optically isolated digital inputs and eight high-power relay outputs in a 145 × 90 × 40 mm enclosure. It delivers maximum Modbus-RTU I/O density for PLC expansion, building automation, and large-scale telemetry systems.

ModelDIDOAITypical Role
Y301-88088 (SPDT)Multi-zone digital automation

Positioning Highlights

  • Largest I/O count in the Y301 series for pure digital control
  • Independent indicators for all 16 channels plus system status LEDs
  • Robust automation firmware with 16 linkage rules and DO retention

2. Ordering Information

2.1 Model Naming

Y301-880-IF

  • IF → Interface option: RS485 (default), RS232, or TTL

2.2 SKU Matrix

SKUInterfaceDescription
Y301-880-RS485RS485Multi-drop bus deployment
Y301-880-RS232RS232Point-to-point / HMI integration

2.3 Package Contents

Module, digital quick reference, warranty leaflet. Optional accessories: DIN clips, USB-RS485 converter, 24 VDC supply, shielded RS485 cabling kit.


3. Key Features

  1. 16-Point Digital I/O – Eight dry/wet DI channels plus eight SPDT relay outputs.
  2. High-Power Relays – AC 277V/10A or DC 28V/10A per channel with independent COM/NO/NC terminals.
  3. Automation Engine – Up to 16 linkage rules (two per DO) covering follow, pulse, timer, logic, and schedule modes.
  4. Scalable Addressing – Software Modbus address 1–255 plus 5-bit DIP offset (0–31) for panel deployments.
  5. Industrial Build – 5–36V DC input, -40°C~85°C, hardware watchdog, reload button, surge-protected communications.

4. Technical Specifications

4.1 Electrical & Environmental

ParameterSpecification
Supply VoltageDC 5~36V
Typical Current260 mA @ 12V
Max Current350 mA @ 12V (all relays energized)
Operating Temperature-40°C ~ +85°C
Humidity5~95% RH, non-condensing

4.2 Digital Inputs

ItemSpecification
Channels8
TypeDry/wet contact, optically isolated
Voltage Range5~36V (wet mode)
Input Current<5 mA/channel
Sampling Rate100 Hz
Pulse Counter32-bit per channel
Debounce5–255 ms (default 50 ms)

4.3 Digital Outputs

ItemSpecification
Channels8 × SPDT relays
Contact RatingAC 277V 10A / DC 28V 10A
Minimum LoadAC 10V 10 mA
Switching Time<10 ms pickup / <5 ms release
Electrical Endurance100k cycles @ rated load
State RetentionNone / soft reboot / full

4.4 Communication

ItemSpecification
InterfaceRS485 (2-wire), RS232, TTL optional
ProtocolModbus-RTU slave
Baud Rate600–230400 bps (default 9600)
Slave Address1–255 (software) + DIP offset 0–31

5. Interface & Pin Description

5.1 Terminal Summary

GroupDescription
PowerV+, V- screw terminals + DC 5.5×2.1 mm jack
DIP SwitchSW1–SW5 (binary address offset)
ReloadHold 3–15 s to restore factory defaults
DICOM+, COM-, DI1~DI8
DONCn / COMn / NOn for channels 1–8
CommunicationA/B/GND (RS485) or TX/RX/GND (RS232/TTL)

5.2 Wiring Guidance

  • Use 20–16 AWG power wiring with an upstream 2 A fuse.
  • Dry DI: bridge COM+ to DI through contact closure; wet DI: external 5–36V referenced to COM-.
  • DO: add RC snubbers (AC) or flyback diodes (DC) for inductive loads; keep loads within relay ratings.
  • RS485: shielded twisted pair, 120 Ω termination at both bus ends with common reference ground.

6. Mechanical & Environmental

Y301-880 Dimensions

ItemValue
Dimensions145 × 90 × 40 mm
Mounting35 mm DIN rail clip or screw slots
ProtectionIP20
EnclosureUL94 V-0 flame-retardant plastic

Maintain ≥20 mm clearance above/below, ≥10 mm at sides, and ≥60 mm at the front for wiring and airflow.


7. Automation & Linkage Rules

ModeDescription
DI FollowDO mirrors one or more DI states
Pulse OutputConfigurable ON/OFF pulse widths
Delay ControlProgrammable on/off delays
Cyclic TogglePeriodic ON/OFF cycling
Timer / ScheduleCalendar-based activation window
Button ModeMomentary pushbutton behavior
Logic ModeAND/OR/XOR combinations
Watchdog ModeAuto-reset DO if DI timeout occurs
  • 16 rules maximum (2 per DO channel)
  • Rules execute locally without host polling
  • DO retention stores last automation state if enabled

  • Manufacturer: Hunan Yanji Tech Co.,Ltd