Appearance
Y301-600/800/G00 Series Digital Input Module
Product Manual
| Y301-600 | Y301-800 | Y301-G00 |
|---|---|---|
![]() | ![]() | ![]() |
Manufacturer: Hunan Yanji Tech Co.,Ltd
address: Room 21014, Unit 1, Fudixingguang plaza, Yuhua district Yingxin road, Changsha, Hunan, p.r. China Email: hi@yanjiiot.com
Website: www.yanjiiot.com
Table of Contents
- Product Features
- Product Functions
- Product Selection
- Main Parameters
- Interface Description
- Input Wiring
- Communication Wiring
- Testing Software
- Parameter and Working Mode Configuration
- Development Resources
- FAQ and Solutions
- Technical Support
1. Product Features
- Power Supply Voltage: DC 7-30V
- 8-Channel Isolated Optocoupler Input
- Communication Baud Rate: 2400, 4800, 9600, 19200, 38400 (default 9600, configurable)
- Communication Protocol: Supports standard Modbus RTU and Modbus ASCII protocols
- Device Address: Configurable 0-255 addresses via software
2. Product Functions
Eight optocoupler isolated inputs, compatible with dry contacts and DC 3.3-24V voltage signals.
3. Product Selection
| Model | Modbus | RS232 | RS485 | USB | WiFi | Output | Input |
|---|---|---|---|---|---|---|---|
| Y301-600-RS232 | ● | ● | 0 | 6 | |||
| Y301-600-RS485 | ● | ● | 0 | 6 | |||
| Y301-800-RS232 | ● | ● | 0 | 8 | |||
| Y301-800-RS485 | ● | ● | 0 | 8 | |||
| Y301-G00-RS232 | ● | ● | 0 | 16 | |||
| Y301-G00-RS485 | ● | ● | 0 | 16 |
4. Main Parameters
| Parameter | Description |
|---|---|
| Data Interface | RS485, RS232 |
| Rated Voltage | DC 7-30V |
| Power Indicator | 1× LED indicator |
| Temperature Range | Industrial grade, -40°C ~ 85°C |
| Dimensions | 120×70×35mm |
| Installation Method | 35mm DIN rail mounting |
| Default Communication Format | 9600, n, 8, 1 |
| Baud Rate | 2400, 4800, 9600, 19200, 38400 |
| Software Support | Configuration software, control software; Supports various SCADA software; Supports LabVIEW, etc. |
| Weight | 60g |
5. Interface Description

Interface Description:
| Terminal | Description |
|---|---|
| VIN | Power supply positive (DC 7-30V) |
| GND | Power supply negative (ground) |
| DI1-DI8/DI16 | Digital input channels |
| COM | Common ground for digital inputs |
| A / 485+ | RS485 positive signal (RS485 version) |
| B / 485- | RS485 negative signal (RS485 version) |
| TX | Transmit data (RS232 version) |
| RX | Receive data (RS232 version) |
| GND | Communication ground |
Communication Protocols:
- Modbus RTU & ASCII
- RS485 / RS232
6. Input Wiring
6.1 Active Input Wiring (Wet Contact)

Connection Method:
- Connect sensor positive output to DI channel
- Connect sensor negative to COM terminal
- Supports DC 3.3-24V active signals
Applications:
- Proximity sensors
- Photoelectric sensors
- PLC output signals
- Active signal sources
6.2 Passive Input Wiring (Dry Contact)

Connection Method:
- Connect switch/contact between DI channel and external power supply
- Connect COM to ground
- Requires external power supply (3.3-24V)
Applications:
- Mechanical switches
- Push buttons
- Relay contacts
- Limit switches
- Door/window contacts
7. Communication Wiring
7.1 RS485 Cascade Wiring

Wiring Method:
- Connect all A terminals together (daisy chain)
- Connect all B terminals together (daisy chain)
- Connect all GND terminals together
- Add 120Ω termination resistors at both ends of the bus
- Use shielded twisted pair cable
- Maximum 32 devices on one RS485 bus
- Maximum cable length: 1200m @ 9600 bps
7.2 RS232 Connection

Connection Method:
- Module TX to Host RX
- Module RX to Host TX
- Module GND to Host GND
- Point-to-point connection only
- Maximum cable length: 15m
8. Testing Software
8.1 Software Download
Software Download Link:
http://www.juyingele.com.cn/software/software/聚英翱翔DAM调试软件使用教程.rar
Alternative: Contact technical support for JYDAM debugging software
8.2 Software Interface
JYDAM Debugging Software:

Toolbar Functions:
| Toolbar | Description |
|---|---|
| Communication Settings | Select serial/network communication mode; Select port number/TCP address; Set AI/DI/DO refresh time |
| DO Control | Operate DO channels; Select DO mode; Set action time |
| DI Input | View DI input status; Read DI status to generate query commands; Set DI/DO channel names |
| Analog Input | Display 4-20mA/0-10V/0-5V real-time data/curves; Display PT100/K-type thermocouple/DS18B20 temperature data/curves; Display real-time acquisition time; Set AI/temperature channel names; Set AI channel range conversion and display units; Manually export Excel table data; Manually save data curves |
| Analog Output | Set AO output; Generate AO multi-channel output commands |
| Configuration Parameters | Display current device AI/DI/DO channel quantity information; Set baud rate; Set offset address; Set working mode; Set AI/DI/DO automatic return; Set DO power-off memory |
| Command Area | Generate AI/DI/DO/AO/parameter setting commands |
| Debug Area | User-defined send command testing |
8.3 Communication Testing
Testing Steps:
- Select the device's current serial port (or enter IP address for network)
- Select default baud rate 9600
- Open port
- Receive commands on the right side; if you can control relays, communication is successful

8.4 Digital Input Data Display
Steps:
- Select Digital Input tab
- View data values and real-time status in the lower section

9. Parameter and Working Mode Configuration
9.1 Device Address
9.1.1 Device Address Introduction
- DAM series device default address is 1
- Broadcast address 254 can be used for communication
- Address 0 cannot be used for communication
- Effective Device Address = Offset Address
9.1.2 Reading Device Address
After normal communication, enter initial device address as 254, then click "Configuration Parameters" in the software to read the current device address.


9.1.3 Setting and Reading Offset Address
Click "Read" or "Set" next to the offset address in the JYDAM debugging software to read or set the device's offset address.

9.2 Baud Rate Reading and Setting
Click "Read" and "Set" in the baud rate setting bar to read and set the baud rate and address respectively. After operation, restart the device and modify the computer serial port settings.

10. Development Resources
Detailed Modbus protocol information, register maps, and command examples are provided in the Technical Manual.
For complete development resources, please refer to:
- Y301-600/800/G00 Technical Manual
- Modbus Protocol Chinese Version: http://www.juyingele.com.cn/software/software/Modbus POLL软件及使用教程.rar
11. FAQ and Solutions
11.1 RS232 Communication - Device Not Responding
Solution:
Device and host communication uses RS232 straight-through cable:
- RX to RX
- TX to TX
- GND to GND
11.2 Can Only Turn On, Cannot Turn Off
Troubleshooting:
- Check if the read address matches the actual device address
- Check if there are return commands in the debug information bar
- Verify if return commands are correct
- If address reading fails, no return commands, or abnormal return commands, check communication cables and communication converter
11.3 Multiple Devices on RS485 Bus
Important Notes:
- Each device address must be unique
- Cannot use broadcast address 254 when multiple devices are on the bus
- Broadcast address can only be used when there is only one device on the bus
- When more than 1 device exists, use DIP switch to distinguish addresses for control
- Otherwise, modules may not execute commands correctly due to communication data judgment synchronization issues
12. Technical Support
Contact Information:
- Phone: 4006688400, 010-82899827/1-803
- QQ: 2984784459
- Website: www.juyingele.com.cn
Shandong Huayun IoT Technology Co., Ltd.
- Tel: 0531-58255718 / 0531-55796688
- Email: sales@yanjiiot.com
- Website: www.yanjiiot.com
Disclaimer
Shandong Huayun IoT Technology Co., Ltd. provides this documentation to support customer product design. The company assumes no responsibility for personal injury or property damage caused by improper operation. The company reserves the right to modify specifications without prior notice.
Revision History
| Version | Date | Description | Author |
|---|---|---|---|
| V1.0.0 | 2024-11 | Initial English release for Y301-600/800/G00 series | Technical Documentation Team |
End of Product Manual