Appearance
Y301-006/008/00G Series Analog Input Module
Product Manual
| Y301-006 | Y301-008 | Y301-00G |
|---|---|---|
![]() | ![]() | ![]() |
Manufacturer: Hunan Yanji Tech Co.,Ltd
address: Room 21014, Unit 1, Fudixingguang plaza, Yuhua district Yingxin road, Changsha, Hunan, p.r. China Email: hi@yanjiiot.com
Website: www.yanjiiot.com
Table of Contents
- Product Features
- Product Functions
- Product Selection
- Main Parameters
- Interface Description
- Input Wiring
- Communication Wiring
- Testing Software
- Parameter and Working Mode Configuration
- Development Resources
- FAQ and Solutions
- Technical Support
1. Product Features
- Power Supply Voltage: DC 7-30V
- 16-Channel Analog Input (model dependent: 6, 8, or 16 channels)
- Input Types: Supports 4-20mA current and 0-10V voltage
- High Precision: 16-bit ADC resolution
- Communication Baud Rate: 2400, 4800, 9600, 19200, 38400 (default 9600, configurable)
- Communication Protocol: Supports standard Modbus RTU and Modbus ASCII protocols
- Device Address: Configurable 0-255 addresses via software
2. Product Functions
Multi-channel analog input acquisition module supporting both current (4-20mA) and voltage (0-10V) input modes. Each channel can be independently configured for different input types.
Key Capabilities:
- Simultaneous multi-channel analog signal acquisition
- Independent channel configuration
- High-precision 16-bit ADC conversion
- Real-time data monitoring and logging
- Compatible with various sensors and transmitters
3. Product Selection
| Model | Modbus | RS232 | RS485 | USB | WiFi | Output | Input (AI) |
|---|---|---|---|---|---|---|---|
| Y301-006-RS232 | ● | ● | 0 | 6 | |||
| Y301-006-RS485 | ● | ● | 0 | 6 | |||
| Y301-008-RS232 | ● | ● | 0 | 8 | |||
| Y301-008-RS485 | ● | ● | 0 | 8 | |||
| Y301-00G-RS232 | ● | ● | 0 | 16 | |||
| Y301-00G-RS485 | ● | ● | 0 | 16 |
4. Main Parameters
| Parameter | Description |
|---|---|
| Data Interface | RS485, RS232 |
| Rated Voltage | DC 7-30V |
| Power Indicator | 1× LED indicator |
| Temperature Range | Industrial grade, -40°C ~ 85°C |
| Dimensions | 120×70×35mm |
| Installation Method | 35mm DIN rail mounting |
| Default Communication Format | 9600, n, 8, 1 |
| Baud Rate | 2400, 4800, 9600, 19200, 38400 |
| Analog Input Channels | 6 (Y301-006), 8 (Y301-008), 16 (Y301-00G) |
| Input Types | 4-20mA current, 0-10V voltage |
| ADC Resolution | 16-bit |
| Accuracy | ±0.1% FS |
| Sampling Rate | 10Hz per channel |
| Software Support | Configuration software, control software; Supports various SCADA software; Supports LabVIEW, etc. |
| Weight | 80g |
5. Interface Description
Interface Layout:
| Terminal | Description |
|---|---|
| VIN | Power supply positive (DC 7-30V) |
| GND | Power supply negative (ground) |
| AI1+ to AI16+ | Analog input positive terminals (channel dependent) |
| AI1- to AI16- | Analog input negative terminals (channel dependent) |
| A / 485+ | RS485 positive signal (RS485 version) |
| B / 485- | RS485 negative signal (RS485 version) |
| TX | Transmit data (RS232 version) |
| RX | Receive data (RS232 version) |
| GND | Communication ground |
Communication Protocols:
- Modbus RTU & ASCII
- RS485 / RS232
6. Input Wiring
6.1 Current Input (4-20mA)
Connection Method:
- Connect transmitter positive (+) to AI+ terminal
- Connect transmitter negative (-) to AI- terminal
- Ensure transmitter is powered appropriately
- Configure channel for current mode via software
Applications:
- Temperature transmitters
- Pressure transmitters
- Flow meters
- Level transmitters
- pH sensors with current output
Wiring Notes:
- Use shielded twisted pair cable for long distances
- Keep signal cables away from power cables
- Maximum loop resistance: 500Ω
- Input impedance: <100Ω
6.2 Voltage Input (0-10V)
Connection Method:
- Connect sensor positive output to AI+ terminal
- Connect sensor negative output to AI- terminal
- Configure channel for voltage mode via software
Applications:
- Temperature sensors with voltage output
- Humidity sensors
- Pressure sensors with voltage output
- Position sensors
- Potentiometers
Wiring Notes:
- Use shielded cable for noise immunity
- Input impedance: >100kΩ
- Maximum input voltage: ±15V (protected)
- Minimum source impedance: <1kΩ
6.3 Mixed Configuration Example
Example Setup (Y301-008):
- AI1: Temperature transmitter (4-20mA, 0-100°C)
- AI2: Pressure sensor (0-10V, 0-10 bar)
- AI3: Humidity sensor (0-10V, 0-100% RH)
- AI4: Flow meter (4-20mA, 0-1000 L/min)
- AI5: Level transmitter (4-20mA, 0-5m)
- AI6: pH sensor (4-20mA, pH 0-14)
- AI7: Conductivity sensor (4-20mA)
- AI8: Turbidity sensor (0-10V)
7. Communication Wiring
7.1 RS485 Cascade Wiring
Wiring Method:
- Connect all A terminals together (daisy chain)
- Connect all B terminals together (daisy chain)
- Connect all GND terminals together
- Add 120Ω termination resistors at both ends of the bus
- Use shielded twisted pair cable
- Maximum 32 devices on one RS485 bus
- Maximum cable length: 1200m @ 9600 bps
Best Practices:
- Use high-quality shielded twisted pair cable (e.g., Belden 9841)
- Maintain proper cable impedance (120Ω characteristic impedance)
- Avoid star or tree topologies; use linear daisy-chain only
- Keep stub lengths as short as possible (<1m)
- Ensure proper grounding at one point only
7.2 RS232 Connection
Connection Method:
- Module TX to Host RX
- Module RX to Host TX
- Module GND to Host GND
- Point-to-point connection only
- Maximum cable length: 15m
8. Testing Software
8.1 Software Download
Software Download Link:
http://www.juyingele.com.cn/software/software/聚英翱翔DAM调试软件使用教程.rar
Alternative: Contact technical support for JYDAM debugging software
8.2 Software Interface
JYDAM Debugging Software Features:
| Feature | Description |
|---|---|
| Communication Settings | Configure serial port, baud rate, device address |
| Analog Input Display | Real-time display of AI values in engineering units |
| Data Logging | Record and export data to Excel |
| Curve Display | Real-time trend curves for all channels |
| Channel Configuration | Set input type (4-20mA or 0-10V) for each channel |
| Scaling Configuration | Configure engineering unit conversion |
| Calibration | Perform zero and span calibration |
| Command Generator | Generate Modbus commands for testing |
8.3 Communication Testing
Testing Steps:
- Select the device's current serial port
- Select default baud rate 9600
- Enter device address (default: 1, or use broadcast address 254)
- Open port
- Click "Read AI" to read analog input values
- If values are displayed correctly, communication is successful
8.4 Analog Input Data Display
Display Features:
- Real-time numerical display for all channels
- Graphical trend curves
- Min/Max/Average values
- Configurable update rate
- Engineering unit display
- Data export to Excel
9. Parameter and Working Mode Configuration
9.1 Device Address
9.1.1 Device Address Introduction
- DAM series device default address is 1
- Broadcast address 254 can be used for communication
- Address 0 cannot be used for communication
- Effective Device Address = Offset Address
9.1.2 Reading Device Address
After normal communication, enter initial device address as 254, then click "Configuration Parameters" in the software to read the current device address.
9.1.3 Setting and Reading Offset Address
Click "Read" or "Set" next to the offset address in the JYDAM debugging software to read or set the device's offset address.
9.2 Baud Rate Reading and Setting
Click "Read" and "Set" in the baud rate setting bar to read and set the baud rate. After operation, restart the device and modify the computer serial port settings.
Supported Baud Rates:
- 2400 bps
- 4800 bps
- 9600 bps (default)
- 19200 bps
- 38400 bps
9.3 Channel Configuration
Input Type Configuration: Each channel can be independently configured for:
- Current input (4-20mA)
- Voltage input (0-10V)
Scaling Configuration:
- Set engineering unit range (e.g., 0-100°C for temperature)
- Configure decimal places
- Set display units
Calibration:
- Zero calibration: Apply 4mA or 0V and calibrate
- Span calibration: Apply 20mA or 10V and calibrate
10. Development Resources
Detailed Modbus protocol information, register maps, and command examples are provided in the Technical Manual.
For complete development resources, please refer to:
- Y301-006/008/00G Technical Manual
- Modbus Protocol Chinese Version: http://www.juyingele.com.cn/software/software/Modbus POLL软件及使用教程.rar
11. FAQ and Solutions
11.1 RS232 Communication - Device Not Responding
Solution:
Device and host communication uses RS232 straight-through cable:
- RX to RX
- TX to TX
- GND to GND
11.2 Analog Input Reading Zero or Very Low
Troubleshooting:
- Check sensor wiring connections
- Verify sensor power supply
- Check if channel is configured for correct input type (4-20mA vs 0-10V)
- Test sensor output with multimeter
- Verify sensor is functioning properly
- Check for broken wires or poor connections
11.3 Analog Input Reading Maximum or Very High
Troubleshooting:
- Check for short circuits in wiring
- Verify input type configuration matches sensor output
- Check sensor output range
- Verify proper grounding
- Check for electromagnetic interference
11.4 Unstable or Noisy Readings
Troubleshooting:
- Use shielded cable for all analog inputs
- Keep analog signal cables away from power cables
- Verify proper grounding (single-point ground)
- Check for loose connections
- Add filtering in software if necessary
- Check sensor power supply stability
- Verify proper cable termination
11.5 Multiple Devices on RS485 Bus
Important Notes:
- Each device address must be unique
- Cannot use broadcast address 254 when multiple devices are on the bus
- Broadcast address can only be used when there is only one device on the bus
- When more than 1 device exists, use unique addresses for each device
- Add 120Ω termination resistors at both ends of the bus
12. Technical Support
Contact Information:
- Phone: 4006688400, 010-82899827/1-803
- QQ: 2984784459
- Website: www.juyingele.com.cn
Shandong Huayun IoT Technology Co., Ltd.
- Tel: 0531-58255718 / 0531-55796688
- Email: sales@yanjiiot.com
- Website: www.yanjiiot.com
Disclaimer
Shandong Huayun IoT Technology Co., Ltd. provides this documentation to support customer product design. The company assumes no responsibility for personal injury or property damage caused by improper operation. The company reserves the right to modify specifications without prior notice.
Revision History
| Version | Date | Description | Author |
|---|---|---|---|
| V1.0.0 | 2024-11 | Initial English release for Y301-006/008/00G series | Technical Documentation Team |
End of Product Manual