Skip to content

IO Controller (Y301)

IO Controller

The Y301 series products support multi-channel dry/wet node detection, supports multi-channel relay outputs, analog inputs(in cludes voltage and current), and digital inputs. They support the standard Modbus-RTU protocol and can read and control IO status through the product's upper computer or third-party configuration software.

Models

DI CountDO CountAI Count
Y301-220220
Y301-222222
Y301-440440
Y301-444444
Y301-880880

Main Features

  • Supports standard Modbus-RTU protocol
  • Supports upper computer configuration, seamless integration with third-party LabVIEW, PLC, and various configuration software
  • 5V~36V industrial-grade wide voltage power supply
  • -40℃~85℃ industrial-grade operating environment
  • Optional RS485 version, RS232 version, TTL version
  • Switch input interface (DI) with opto-isolation, supports dry and wet contact input
  • Analog acquisition interface (AI) supports selectable voltage and current input
  • Rich linkage rules to meet automation control in various scenarios
  • Supports DI rising edge and falling edge counting function
  • Supports switch output interface (DO) to maintain state after restart
  • Hardware watchdog for stable operation without downtime
  • Supports DIP switch and command configuration for slave address
  • Supports rail and cabinet installation

Parameters

ItemValue
Power Supply VoltageDC 5-36V
DO Contact CapacityAC 277V 10A
DC 28V 10A
AI Range0~10V
4~20mA
Operating Temperature-40~85℃
Operating Humidity5%~95%
Hardware InterfaceRS485 (optional RS232 version)
Baud Rate600~230400 (default 9600)
Data Bits8, 9 (default 8)
Stop Bits1, 2 (default 1)
Parity BitNone/Odd/Even (default None)
Communication ProtocolModBus RTU